GLC125

Standby or Prime Power Features

Gen Set Ratings

Natural Gas LP Gas
Model GLC125 150˚C Rise 105˚C Rise 150˚C Rise 105˚C Rise
Standby Rating Prime Rating Standby Rating Prime Rating
Generator Voltage Phase Hz kW/kVA Amps kW/kVA Amps kW/kVA Amps kW/kVA Amps
120/208 3 60 125/156 434 110/138 382 110/138 382 100/125 347
127/220 3 60 125/156 410 115/144 377 110/138 361 100/125 328
UCI274E 120/240 3 60 125/156 376 110/138 331 110/138 331 100/125 301
139/240 3 60 130/163 391 115/144 346 110/138 331 100/125 301
220/380 3 60 125/156 237 110/138 209 105/131 199 95/119 181
277/480 3 60 130/163 195 115/144 173 110/138 165 100/125 150
UCI274E 120/240 1 60 115/115 479 100/100 417 105/105 438 100/100 417
IMPORTANT NOTES:
• For ratings and voltages not listed above consult Factory

Controls Digital Control Module

Controller • Fully configurable from front panel keypad
• Microprocessor-based circuitry • Password protected
• Standard features meet requirements of NFPA110 Level 1 • Low Oil Pressure Alarm Light
• Backlit LCD display •High Coolant Temperature Alarm Light
•Digital 3-phase voltage, current & frequency metering • Overspeed Alarm Light
•Up to 28 alarm/shutdown fault circuits analog/digital inputs
• EMI/RFI noise immunity per IEEE C62.41 Shutdowns
• Certified to UL #508 • Overspeed
• Over-crank
Standard Features • Loss of speed signal
•Timers – Engine start, Cooldown, Oil Bypass, Cycle crank •High engine temperature
• Control switches – Run/Auto/Load test, horn test, Lamp test, Common • Low Oil Pressure Shutdown
• LCD Display menu – AC metering, timer, Alarm/shutdown, engine •Emergency stop
• Diagnostic LED indicators – Watchdog (CPU running), run output
energized, remote start signal initiated, common fail output energized

Engine Technical Data

Manufacturer General Motors
Engine Model & Type Vortec, 4 cycle, Turbo-Charged
Cylinder Configuration V-8
Displacement - cu. in.(Liters) 496 (8.1)
Bore and Stroke - in. - mm 4.25 x 4.37 (107.95 x 111)
Compression ratio 9.1:1
Water pump type Centrifugal
Piston speed, M/sec. (ft./min) 6.66 (1311)
Rated rpm 1800
Max. power at rated rpm, kW (Hp) 149 (200)
Fuel type LP Gas or Natural Gas
Governor type Electronic
Governor make Woodward
Frequency regulation, steady state +/- 0.5%
Frequency regulation, no load to full load Isochronous
Air filter type Dry
Oil pan capacity qt (L) 8.0 (8.5)
Oil pan capacity w/filter – qt – liters 8.5 (9.0)
Oil Filter: quantity, type 1, Cartridge
Rec'd oil type - SF/CC/CD-10°F to 90°F 5W-30

Battery charging alternator:

- Ground (negative/positive) Negative
- Volts (DC) 12
- Ampere rating 70
Battery voltage 12VDC

Gen Set Technical Data

Alternator Technical Data

Generator Frame 274 Voltage Regulation NL - FL +/- 1.5%
Exciter Brushless Underspeed Protection Standard
Cooling Fan Cast alloy aluminum Overexcitation Protection Standard
Bearing Single, double shielded Overvoltage Protection Optional
Connection Type Reconnectable Loss of Sensing Protection Standard
Insulation Type Class H Overspeed 2250 RPM
Windings 100% copper Standards NEMA, IEC, IEEE,CSA,BS
Pitch 2/3 Phase Sequence A(U),B(V),C(W)
Amortisseur Winding Full TIF (1960 Weightings) <50
Voltage Regulator SX460 Excitation System PMG - optional
SKVA output with 30% voltage dip max. 480V @ 60 Hz = 450

Fuel System Requirements

Fuel Type LP Gas or Natural Gas
Fuel supply line inlet 2” NPTF
Natural gas/LpG fuel supply pressure, oz./in.2 (in H2O) 1.74 – 2.74 (7.0 – 11.0)

NOTE: Ratings based on 60 Hz

Exhaust System Requirements
Exhaust flow at rated kW, m3/min. (cfm) 26.1 (920)
Exhaust temperature at rated kW, 650 (1200)
dry exhaust, °C (°F)
Maximum allowable back pressure, kPa (in. Hg) 10.2 (3.0)
Exhaust outlet size at engine hookup, mm (in.) 73 (2.9)
Fuel Consumption Natural Gas, m3/hr. (cfh) at % Load LP Gas, m3/hr. (cfh) at % Load
Standby Rating @ 60 Hz Prime Rating @ 60 Hz Standby Rating @ 60 Hz Prime Rating @ 60 Hz
100% 46.8 (1651) 44.0 (1553) 16.5 (582) 15.4 (543)
75% 38.9 (1372) 35.2 (1244) 13.3 (469) 12.3 (435)
50% 27.9 (984) 26.5 (934) 10.0 (226) 9.3 (327)
25% 18.4 (369) 17.7 (625) 6.4 (226) 6.2 (219)

Cooling (Standard Radiator) Engine Operational Values

Ambient temperature, °C (°F) 40 (104)
Engine jacket water capacity, L (gal.) 10.0 (2.6)
Radiator system capacity, including engine, L (gal.) Engine jacket water flow, Lpm (gpm) 24.2 (6.4) 144 (38)
Heat rejected to cooling water at rated kW, dry exhaust, kW (Btu/min.) 110 (6260)
Water pump type Centrifugal
Fan diameter including blades, mm (in.) 609 (24)
Fan, kWm (Hp) 10.3 (13.8)
Max. restriction of cooling air, intake and discharge side of radiator, Kpa (in. H2O) 0.125 (.5)
Air Requirements 60 Hz
Radiator-cooled cooling air – m3/min. (scfm) Combustion air required – m3/min. (cfm) Heat rejected to ambient, engine – Btu/min (kW) 306 (10800) 10.0 (353) 72 (4100)
Heat rejected to ambient, generator – Btu/min (kW) 12.5 (711)

NOTE: Power corrected for ambient conditions per engine manufacturer’s recommendations.

Accessories and Options

Control Panel Generator Accessories Engine Fuel System
High Coolant Temp. Pre-alarm Main Line Circuit Breaker Flexible Fuel Lines
Low Oil Pressure Pre-alarm Shunt Trip
Alarm Horn with Switch Alternator Heater
Remote Start-Stop Field Circuit Breaker Miscellaneous
Remote Annunciator PMG Weather protective Enclosure
Sound Attenuated Enclosure
PER NFPA 110 Vibration Isolators
Run Relay Engine Electrical System Coolant Heater
Dry Contacts Batteries
Battery Rack
Engine Exhaust System Battery Cables
Industrial Silencer Battery Charger - Automatic
Residential Silencer Battery Charger - Trickle
Critical Silencer
Exhaust Flex
Rain Cap

Dimensions – in (mm)

Weight – lbs. (Kg) 4000 (1818)

Cubes (Approximate) 127 ft

*Open unit configuration, accessories not included

Ratings – Standby Ratings: Standby ratings are applicable for supplying emergency power for the duration of a utility power outage. Primary power to the installation is utility supplied. No overload capability for standby rating. Standby ratings in accordance with ISO 3046, BS55114, DIN 6271. Continuous Power Rating: Continuous power is the maximum power available for continuous duty. A 10% overload capacity is available for 1 hour out of 12 hours of operation. Prime Power ratings in accordance with ISO 3046, BS55114, DIN 6271. For additional information, please consult factory. Manufacture reserves the right to implement specifications or design changes without notice.